Clean the heat exchanger
What is going on
Remove the heat exchanger assembly for cleaning. Protect the floor in front of the furnace.
Likely causes
- Soot or scale buildup in the heat exchanger
Check in this order
- Turn off electrical and gas supply to the furnace.
- Remove the burner access panel and label, then disconnect gas valve wires.
- Disconnect the gas supply line from the gas valve.
- Disconnect the flame sensor wire, ignitor 2-pin plug and rollout switch wires.
- Remove the four burner assembly screws and remove the gas valve, manifold and burner box as one unit.
- Clean the burners if needed using the burner cleaning procedure.
- Remove the condensate trap and the flue collar. Disconnect the condensate drain tubes and the exhaust collar clamps.
- Disconnect the combustion air inducer, pressure switch wiring and combustion air tubing.
- Remove the junction box, wiring, primary limit and top cap as needed.
- Remove the vestibule and heat exchanger assembly from the cabinet.
- Backwash the heat exchanger with soapy water or steam below 275 °F (135 °C), then rinse and drain it fully.
- Reinstall all parts in reverse order, making sure the rear baffle sits under the support at the rear of the cabinet.
- Reconnect gas and electrical supplies, verify connections, then light the furnace and run it for 5 minutes to confirm it is clean and dry.
Applies to: Heat exchanger cleaning
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Allied 92G1UH installation instructions manual, p. 51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.