Allied · Furnace troubleshooting
Clean the burner assembly
What is going on
Clean the burners and crossovers after removing the burner and manifold assembly.
Likely causes
- Foreign matter blocking the burner ports or crossovers
Check in this order
- Turn off gas and electrical power and remove the heating compartment access panel.
- Disconnect and label the gas valve, ignitor, rollout switch, flame sensor and ground wires.
- Disconnect the gas supply line from the gas valve.
- Remove the four screws holding the burner and manifold assembly to the vestibule. Do not let the ignitor plate dislodge.
- Gently vacuum the burner faces with a soft brush attachment.
- Check inside the burners and crossovers for blockage and clear any found.
- Reinstall the assembly with the existing four screws, reconnect all wires and the gas line.
- Verify gas and electrical connections, then run the furnace for 5 minutes and replace the access panel.
Applies to: Burner cleaning
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Allied 92G1UH installation instructions manual, p. 52. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.