Checking gas flow rate (approximate)

A95A9395G192G1UH

What is going on

Clocking the meter. Quick way to check actual gas input. Run furnace 5 min first so it is steady. Only this appliance on the meter. Compare against the Gas Meter Clocking Chart for the unit size and fuel.

Likely causes

  • Orifices wrong size or partly blocked
  • Manifold pressure off
  • Other gas appliances left running during the test
  • Meter dial misread

Check in this order

  1. Shut off all other gas appliances on the meter, including pilots.
  2. Time two revolutions of the meter dial in seconds.
  3. Divide that time by two to get the time for one revolution.
  4. Compare the result with the Gas Meter Clocking Chart for the unit size and fuel.
  5. If manifold pressure is correct and the flow rate is wrong, check the burner orifices for proper size and restriction.
  6. Remove any temporary gas meter that was installed.
  7. Relight other appliances after the test and leak-check any joint you disturbed.

Applies to: All sizes

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Allied 92G1UH installation manual, p. 47. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.