Rheem · Furnace troubleshooting

Checking furnace input rate

96V96MDV

What is going on

Clocking the gas meter to confirm the Rheem 96V/96MDV isn't over-fired. Input must never go above the rating plate.

Likely causes

  • Manifold pressure set too high
  • Oversized orifices installed
  • Unadjusted for altitude or a different heating value than expected

Check in this order

  1. Make sure all other gas appliances are off, except pilot burners, so the meter reads only the furnace.
  2. Start the furnace and time the meter for one cubic foot of gas.
  3. Compare the calculated input with the rating plate and the input rate table, because the numbers should agree.
  4. If input is high, adjust manifold pressure or orifice size.
  5. Never set input above the rating plate.
  6. This is gas work for a licensed technician. Recheck input after any adjustment.

Applies to: 96V and 96MDV gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: 96V installation instructions, p. 103. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.