Allied · Furnace troubleshooting
Checking a shared vent after this furnace is removed or replaced
What is going on
If this furnace was on a common vent with other gas appliances, the vent may now be too large for the remaining appliances. Test each remaining appliance on its own while the others stay off. Carbon monoxide poisoning can result if this test is skipped.
Likely causes
- Vent sized for the old furnace plus other appliances
- Blockage, restriction, leakage, corrosion or poor horizontal pitch in the vent
Check in this order
- Seal any unused openings in the common vent.
- Inspect the vent for correct size, horizontal pitch, blockage, leakage and corrosion.
- Close building doors, windows and doors to other spaces. Run clothes dryers and non-vented appliances, and run bathroom and range hood exhausts at full speed. Do not run a summer exhaust fan. Close fireplace dampers.
- Light the appliance being checked and set the thermostat so it runs continuously.
- After the main burner has run 5 minutes, check for flue gas leaks at the draft hood relief opening with a match or candle flame.
- Return doors, windows, fans, dampers and other appliances to their previous operation.
- If a venting problem is found, resize the common vent to the minimum size from the tables in Appendix G of ANSI Z223.1 (National Fuel Gas Code).
Applies to: Furnace replacement or removal from a common vent
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Allied 92G1UH installation manual, p. 41. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.