Weil-McLain · Combi boiler troubleshooting

Wrong boiler model shown at power-up

Weil-McLain ECO Tec Series 3

What is going on

The power-up screen shows the boiler model set in the control. If it does not match the rating plate, the boiler can run unsafely.

Likely causes

  • Wrong model picked during setup
  • Control replaced or reset to factory defaults
  • Blower type on a 199/199C does not match the blower installed

Check in this order

  1. Turn the boiler off if the model is wrong.
  2. Compare with the model on the rating plate.
  3. Change it in contractor menu > Boiler Settings > Boiler Model. Choices: ECO Tec 80, 110, 110 Combi, 150, 150 Combi, 199, 199 Combi.
  4. On 199 and 199C you also pick the blower type (EF90 or NG150). Read the blower label and pick the same one.
  5. Changing the model or blower type resets all boiler settings, so go through the setup again after.
  6. Also check Altitude (set it if the site is above 2,000 ft, in 500 ft steps) and Fuel Type.

Applies to: ECO Tec 110C, 150C, 199C Series 3 (combi)

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Control action - Power up, p.3; Boiler Settings, p.58. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.