Weil-McLain · Combi boiler troubleshooting
Blue banner or wrench symbol on the display
What is going on
The maintenance timer ran out (12 months by default). It only shows in standby and the boiler keeps running normally. A blue banner during a heating call is normal and is not this reminder.
Likely causes
- Scheduled maintenance date has passed
Check in this order
- Do the scheduled service.
- Contractor menu > Service Info > Reset Reminder updates the last and next maintenance dates.
- If the homeowner resets it, only the next date moves.
- Set Interval Settings to fit the service history, and enter your name and phone so they show on the reminder and on lockouts.
Applies to: ECO Tec 110C, 150C, 199C Series 3 (combi)
More combi boiler guides
- A sensor is missing from the list at power-up
- Blower calibration will not start
- Boiler fires or pumps run with no call for heat
- Boiler shut down or locked out by an external limit on J20
- Boiler will not fire with a flow switch or damper on J18
- Burner tries to light, then waits about an hour before the next try
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Control action - Standby/Maintenance, p.3; Homeowner menus p.56; Service menus p.72. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.