Weil-McLain · Combi boiler troubleshooting
Boiler will not fire with a flow switch or damper on J18
What is going on
The proof-of-closure circuit on J18 comes with a jumper. A flow switch or combustion air damper end switch can replace it, and the boiler only fires when that contact is closed.
Likely causes
- Flow switch or damper end switch not closing
- Contact not isolated (the circuit runs on 5 VDC)
- Damper not driven because Input/Output 3 is not set up
Check in this order
- Safety first turn off power at the service switch before touching wiring. Gas-side work is for a qualified gas technician only.
- If nothing is wired there, the J18 jumper must be in place.
- The device must give an isolated contact; J18 carries 5 VDC. J18-1 has a PTC that trips at 340 mA (140 mA hold at 20°C).
- Flow switch no control settings needed.
- Damper assign Input 3 as AUX Pump/Output, mode local or System Damper. Output 3 then gives 120 VAC to the damper motor. Use a relay for other voltages or over 2.2 A.
- Multi-boiler system damper proof-of-closure inputs wired in series with the end devices. Local damper: wire each boiler's input on its own, not in series.
Applies to: ECO Tec 110C, 150C, 199C Series 3 (combi)
More combi boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Field wiring J. Proof of closure, p.15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.