Weil-McLain · Combi boiler troubleshooting

Blower calibration will not start

Weil-McLain ECO Tec Series 3

What is going on

Blower calibration in Boiler Settings re-learns the blower for best performance. It only runs with the boiler in standby.

Likely causes

  • A call for heat is active

Check in this order

  1. Turn off all calls for heat (thermostats, DHW) and wait for the display to show Standby.
  2. Then run Blower Calibration from contractor menu > Boiler Settings.
  3. Last Calibration Date in Service Info shows when it was last done.

Applies to: ECO Tec 110C, 150C, 199C Series 3 (combi)

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Boiler Settings, p.58; Service menus, p.72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.