Weil-McLain · Combi boiler troubleshooting
A sensor is missing from the list at power-up
What is going on
When power comes on, the screen lists every sensor the control detects. A sensor that is not listed is not connected right.
Likely causes
- Sensor not plugged in or loose wire
- Sensor wired to the wrong terminals
Check in this order
- Safety first turn off power at the service switch before touching wiring. Gas-side work is for a qualified gas technician only.
- Turn power off and check the missing sensor's wiring.
- System return sensor goes on J19 pins 1-2, system supply sensor on J19 pins 3-4. The outdoor sensor also lands on J19 (see wiring diagram Figure 10).
- System supply and return sensors are required on primary/secondary piping. Put the supply sensor at least 6 pipe diameters but no more than 3 feet downstream of the boiler tee.
- The outdoor sensor ships with the boiler and is required unless the job is exempt.
- Turn power back on and check the list again.
Applies to: ECO Tec 110C, 150C, 199C Series 3 (combi)
More combi boiler guides
- Blower calibration will not start
- Blue banner or wrench symbol on the display
- Boiler fires or pumps run with no call for heat
- Boiler shut down or locked out by an external limit on J20
- Boiler will not fire with a flow switch or damper on J18
- Burner tries to light, then waits about an hour before the next try
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Control action - Power up, p.3; Field wiring D/E, p.13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.