Weil-McLain · Combi boiler troubleshooting

A sensor is missing from the list at power-up

Weil-McLain ECO Tec Series 3

What is going on

When power comes on, the screen lists every sensor the control detects. A sensor that is not listed is not connected right.

Likely causes

  • Sensor not plugged in or loose wire
  • Sensor wired to the wrong terminals

Check in this order

  1. Safety first turn off power at the service switch before touching wiring. Gas-side work is for a qualified gas technician only.
  2. Turn power off and check the missing sensor's wiring.
  3. System return sensor goes on J19 pins 1-2, system supply sensor on J19 pins 3-4. The outdoor sensor also lands on J19 (see wiring diagram Figure 10).
  4. System supply and return sensors are required on primary/secondary piping. Put the supply sensor at least 6 pipe diameters but no more than 3 feet downstream of the boiler tee.
  5. The outdoor sensor ships with the boiler and is required unless the job is exempt.
  6. Turn power back on and check the list again.

Applies to: ECO Tec 110C, 150C, 199C Series 3 (combi)

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Control action - Power up, p.3; Field wiring D/E, p.13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.