Weil-McLain · Combi boiler troubleshooting
Boiler fires or pumps run with no call for heat
What is going on
Two built-in functions can do this. Freeze protection starts the chosen circulators when the heat exchanger sensors drop below 45°F, fires the burner at low fire below 40°F, and stops both above 48°F. Circulator exercising runs each selected pump for 10 seconds after 72 hours with no run time.
Likely causes
- Freeze protection active
- Circulator exercising
Check in this order
- Check boiler water temperature on the information screen. Low readings near 40-48°F point to freeze protection.
- Look at contractor menu > Pump Settings > Freeze Protect Circs and Circulator Exercising to see which pumps are set.
- A 10-second pump run after a long idle period is the exercise function, not a fault.
Applies to: ECO Tec 110C, 150C, 199C Series 3 (combi)
More combi boiler guides
- A sensor is missing from the list at power-up
- Blower calibration will not start
- Blue banner or wrench symbol on the display
- Boiler shut down or locked out by an external limit on J20
- Boiler will not fire with a flow switch or damper on J18
- Burner tries to light, then waits about an hour before the next try
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Pump Settings, p.59. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.