Weil-McLain · Combi boiler troubleshooting

Burner tries to light, then waits about an hour before the next try

Weil-McLain ECO Tec Series 3

What is going on

Each call gets up to 5 light-off tries. After a failed try the gas valve closes, the blower runs a postpurge and the control starts over. After the 5th failure in a row it waits 60 minutes, then tries again on its own.

Likely causes

  • Electrode did not see a flame signal at the end of the ignition period, 5 times in a row

Check in this order

  1. Safety first turn off power at the service switch before touching wiring. Gas-side work is for a qualified gas technician only.
  2. Read the fault name on the home screen before you reset anything.
  3. Hold the WM logo for 7 seconds to open the contractor menu, then go to Diagnostics to see current and past lockouts.
  4. In Boiler Settings, check Boiler Model, Fuel Type (natural gas or propane) and Altitude against the rating plate and the job site. The manual calls these critical settings.
  5. On a 199 or 199C, check that the blower type picked in the control (EF90 or NG150) matches the label on the blower.
  6. Watch one light-off prepurge at ignition speed, then spark and gas valve open together, spark stops and the control checks flame through the electrode.
  7. Flame and lockout fault details are in the ECO Tec Boiler Manual troubleshooting section, not in this manual.

Applies to: ECO Tec 110C, 150C, 199C Series 3 (combi)

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Control action / Sequence of operation, p.3; Contractor menus p.57; Boiler Settings p.58. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.