Weil-McLain · Combi boiler troubleshooting

Thermostat or zone input does not start the boiler

Weil-McLain ECO Tec Series 3

What is going on

Inputs 1-4 are dry-contact inputs. They must never get 24 V from outside.

Likely causes

  • 24 V fed into an input
  • 3-wire zone valve end switch wired straight to an input
  • Input used for something else (combi 3-way valve, AUX output, 0-10V)

Check in this order

  1. Safety first turn off power at the service switch before touching wiring. Gas-side work is for a qualified gas technician only.
  2. Never feed 24 V into Input 1-4.
  3. A thermostat that needs power uses the C terminal. Keep each thermostat at 120 mA or less at 24 VAC. Anticipator setting is 0.1 A.
  4. 3-wire zone valve end switches carry 24 VAC, so use relays to give the control a dry contact.
  5. Combi models input/output pairs 1 and 4 run the combi and 3-way valve and cannot be used for anything else. Use Input 2 for an indirect tank and Input 3 for space heating.
  6. If 0-10 V is used for modulation, Input 2 thermostat no longer creates a call for heat.
  7. With a 0-10 V remote target, a dry-contact demand still has to close on one of the inputs to start a call.
  8. An input assigned to AUX Pump/Output cannot be used as a heat demand.

Applies to: ECO Tec 110C, 150C, 199C Series 3 (combi)

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Field wiring, p.12-13; K. 0-10 VDC remote target, p.15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.