Shadow boiler not showing on the multi-boiler network
What is going on
One ECO Tec master can run up to 8 boilers over RS485. After power-up it can take 30 seconds to 1 minute before the master sees the shadows.
Likely causes
- Duplicate or missing shadow address
- RS485 wiring wrong or looped back to the master
- Communication harness not installed
Check in this order
- Safety first turn off power at the service switch before touching wiring. Gas-side work is for a qualified gas technician only.
- Wait 1 minute after power-up before calling it a fault.
- Give each shadow its own address from 2 to 8. No two boilers can share an address.
- The RS485 harness kit (P/N 383700272) plugs into J12.
- Wire master A2/B2/GND to shadow 2 A2/B2/GND, then shadow 2 A3/B3/GND to shadow 3, and so on.
- Do not run the last shadow back to the master's A3/B3/GND. Ground the drain wire at the last boiler.
- With Unity boilers on the network, the ECO Tec must be the master.
- A boiler that drops off and comes back is put back where it was by the master on its own.
Applies to: ECO Tec 110C, 150C, 199C Series 3 (combi)
More combi boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Multiple boilers / control features, p.4; Multiple boiler communication wiring, p.17-18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.