Weil-McLain · Combi boiler troubleshooting

No space heating in mild weather, display shows WWSD

Weil-McLain ECO Tec Series 3

What is going on

Warm weather shutdown blocks space heating when the outdoor temperature is above the WWSD setting. The boiler sits in standby and the display shows WWSD. DHW and Custom priorities are not blocked.

Likely causes

  • Outdoor temperature is above the WWSD setting
  • Outdoor sensor reading is off

Check in this order

  1. Compare the outdoor temperature on the boiler information screen with WWSD Temp in Boiler Settings.
  2. Lower WWSD or set it to OFF if the customer needs heat at that temperature.
  3. WWSD needs the outdoor sensor. Without a sensor, WWSD must be OFF.
  4. If the outdoor reading looks wrong, use Adjust Outdoor in Boiler Settings to calibrate it.
  5. Check the sensor mounting outside wall, out of direct sun and away from other heat or cooling, wire outlet pointing down.

Applies to: ECO Tec 110C, 150C, 199C Series 3 (combi)

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Control action - WWSD, p.3; Boiler Settings, p.58; Field wiring E, p.13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.