Lockout on the manual reset high temperature limit

Weil-McLain ECO Tec Series 3

What is going on

If boiler outlet water goes over the Manual Reset High Temp Limit setting (200°F from the factory), the control shuts the boiler down and locks out. It needs a manual reset. Weil-McLain does not recommend changing this setting.

Likely causes

  • Boiler outlet water went over the limit setting
  • Limit setting was lowered from the 200°F default

Check in this order

  1. Check the setting contractor menu > Boiler Settings > Manual Reset High Temp Limit.
  2. Look at Boiler Out / Boiler In and Target Temp on the boiler information screen.
  3. Check the target temperatures of each priority. System presets top out at 180°F max target (120°F for slab on grade).
  4. If the system mixes low-temperature circuits (radiant slab) with high-temperature ones, those low circuits need their own limit wired to an external limit input.
  5. Reset at the display. If it keeps tripping, go to the ECO Tec Boiler Manual troubleshooting section.

Applies to: ECO Tec 110C, 150C, 199C Series 3 (combi)

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Wizard screen, p.29; Boiler Settings, p.58; Figure 25 System Type Presets, p.54; Temperature settings note, p.2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.