Weil-McLain · Combi boiler troubleshooting

ECO Tec S2 power-up shows wrong model or missing sensor

Weil-McLain ECO Tec Series 2

What is going on

On power-up the screen shows the boiler model and lists the sensors it finds.

Likely causes

  • Control replaced or reset and set to the wrong boiler model
  • Sensor unplugged or bad connection

Check in this order

  1. Check the model on the power-up screen. If it is wrong, turn the boiler off and set the correct model (control model setting p.105 or a factory reset).
  2. If a sensor you expect (outdoor, system supply/return) is not listed, check its wiring and connector, then cycle power.

Applies to: ECO Tec 110/150/199 Series 2 combi

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Power up p.74; Wizard p.78-80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.