Weil-McLain · Combi boiler troubleshooting
ECO Tec S2 manual reset high temperature limit
What is going on
The control has a manual reset high limit set on the Boiler Settings screen (shown at 200 F on the setting screen in the manual). If boiler water goes over it, the boiler locks out.
Likely causes
- Low or no water flow through the heat exchanger
- Circulator not running or air-bound
- Zone valves closed with no by-pass
- Limit set lower than the system needs
Check in this order
- Check the boiler circulator runs and the system is full and purged of air.
- Check flow on direct-connect piping the rise across the heat exchanger at high fire should be about 20 to 35 F, not more.
- Zone valve systems need a by-pass pressure regulator unless the pump is protected against dead-heading.
- Check the setting under Boiler Settings. It can be lowered for some systems but is a safety setting.
- Fix the cause, then reset the control.
Applies to: ECO Tec 110/150/199 Series 2 combi
More combi boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Boiler settings screen Figure 20 p.17; Wizard boiler settings p.78-80; Direct connect piping p.47. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.