Weil-McLain · Combi boiler troubleshooting

ECO Tec S2 locked out by an external limit (J20)

Weil-McLain ECO Tec Series 2

What is going on

External limits can be wired as manual reset (J20 pins 1-2) or auto reset (J20 pins 3-4). A jumper is fitted from the factory on each pair.

Likely causes

  • Device wired on J20 pins 1-2 opened (manual reset lockout)
  • Device wired on J20 pins 3-4 opened (auto restart)
  • Factory jumper missing

Check in this order

  1. Find which limit is wired to J20 and why it opened.
  2. Pins 1-2 boiler goes into manual lockout and the alarm contact on J18 pins 4-5 closes. The limit must close, then reset the control by hand.
  3. Pins 3-4 boiler stops while the limit is open and restarts on its own 150 seconds after it closes.
  4. No external limit used make sure the factory jumpers are still on both pairs.
  5. The J18 alarm contact closes on manual lockout only (rated 24 VAC or less, 0.5 A or less).

Applies to: ECO Tec 110/150/199 Series 2 combi

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Field wiring F/H p.63-64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.