Weil-McLain · Combi boiler troubleshooting
ECO Tec S2 does not light: 5 tries then 60 minute wait
What is going on
If no flame is proven, the control shuts the gas valve, post-purges and tries again. After 5 failed tries it waits 60 minutes before trying again.
Likely causes
- Gas off or low inlet pressure
- Gas valve throttle/offset out of adjustment (often after a conversion)
- Ignition electrode / flame sensor worn, dirty or gap wrong
- Blocked vent or air intake
- Condensate backed up
Check in this order
- Power off and gas off before opening the boiler.
- Check gas is on and inlet pressure is right at the gas valve inlet test port.
- Check vent and air pipes for blockage, and that the condensate trap and drain are clear.
- Inspect the ignition electrode / flame sensor and its wire.
- If the boiler was just converted, check the gas valve coarse settings (see the gas conversion guide).
- Reset the control from the display and watch the light-off: pre-purge, spark, then flame check.
Applies to: ECO Tec 110/150/199 Series 2 combi
More combi boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Sequence of operation Figure 72 p.74. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.