ECO Tec S2 condensate line blocked or frozen

Weil-McLain ECO Tec Series 2

What is going on

If condensate cannot drain, it can come out of the boiler tee and cause water damage.

Likely causes

  • Frozen or blocked drain line
  • Condensate pump too small or failed

Check in this order

  1. Check the drain line is clear and protected from freezing.
  2. Condensate pump minimum capacity 2 GPH (80), 3 GPH (110), 4 GPH (150), 5 GPH (199), plus any other appliances on the same pump. The pump should have an overflow switch.
  3. Condensate is acidic (pH about 3.2 to 4.5). Use a neutralizer when draining to metal pipe or where code requires.

Applies to: ECO Tec 110/150/199 Series 2 combi

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Condensate drain p.57. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.