Weil-McLain · Combi boiler troubleshooting
ECO Tec S2 condensate line blocked or frozen
What is going on
If condensate cannot drain, it can come out of the boiler tee and cause water damage.
Likely causes
- Frozen or blocked drain line
- Condensate pump too small or failed
Check in this order
- Check the drain line is clear and protected from freezing.
- Condensate pump minimum capacity 2 GPH (80), 3 GPH (110), 4 GPH (150), 5 GPH (199), plus any other appliances on the same pump. The pump should have an overflow switch.
- Condensate is acidic (pH about 3.2 to 4.5). Use a neutralizer when draining to metal pipe or where code requires.
Applies to: ECO Tec 110/150/199 Series 2 combi
More combi boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Condensate drain p.57. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.