ECO Tec S2 combi: recirculation not starting the boiler
What is going on
The combi needs real flow through the DHW side to fire.
Likely causes
- Recirc pump gives less than 0.5 GPM through the boiler
- Mixing valve cutting the flow
- Recirc pump running non-stop
Check in this order
- Check the recirc pump can move 0.5 GPM or more through the boiler, counting the mixing valve's effect on flow.
- Keep the mixing valve's minimum flow.
- Do not run the recirc pump all the time. Use an aquastat (set 5 to 10 F below the mixed outlet), a timer or a smart pump.
- Check the check valves in the recirc loop.
- If there is a back-flow preventer or check valve on the cold inlet, a thermal expansion tank is needed.
Applies to: ECO Tec 110/150/199 Series 2 combi
More combi boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Recirculation p.45-46. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.