Weil-McLain · Combi boiler troubleshooting

ECO Tec S2 combi: recirculation not starting the boiler

Weil-McLain ECO Tec Series 2

What is going on

The combi needs real flow through the DHW side to fire.

Likely causes

  • Recirc pump gives less than 0.5 GPM through the boiler
  • Mixing valve cutting the flow
  • Recirc pump running non-stop

Check in this order

  1. Check the recirc pump can move 0.5 GPM or more through the boiler, counting the mixing valve's effect on flow.
  2. Keep the mixing valve's minimum flow.
  3. Do not run the recirc pump all the time. Use an aquastat (set 5 to 10 F below the mixed outlet), a timer or a smart pump.
  4. Check the check valves in the recirc loop.
  5. If there is a back-flow preventer or check valve on the cold inlet, a thermal expansion tank is needed.

Applies to: ECO Tec 110/150/199 Series 2 combi

More combi boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Recirculation p.45-46. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.