TXV coil: high suction pressure, low superheat
What is going on
What causes high suction with low superheat (flooding) on a TXV coil.
Likely causes
- TXV too big
- TXV seat leaking
- TXV superheat set too low
- Bulb not making good contact (loose clamp), not insulated, or in a warm spot
- Weak compressor
- Equalizer in the wrong spot (must be on the suction manifold after the last feeder tube)
Check in this order
- Refrigerant work only by a certified tech. R-454B is mildly flammable: no open flame or sparks near a leak.
- Check the bulb clamp, insulation and location first.
- Check the equalizer line location.
- Check the compressor's pumping capacity.
- Then look at TXV size, setting and seat leakage.
Applies to: NAM24B, NAM36B, NAM36C, NAM48C, NAM59C, NAM59D cased coils with TXV and refrigerant leak sensor
More air handler guides
- Air handler or outdoor unit locks out, or transformer burns out (separate transformers)
- Blower does not run, no heat or no cooling: first checks
- Blower runs nonstop and outdoor unit will not start (leak mitigation)
- Electric heat model: constant torque blower motor not running
- Electric heat model: ECM blower motor not running
- Electric heat model: no 24 V control power
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAM Series cased coil (24-60K, R454B) Installation and Operation Manual, Additional TXV Troubleshooting p.19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.