Navien · Air handler troubleshooting

Electric heat model: ECM blower motor not running

Navien NAS

What is going on

ECM motor checks with line voltage present.

Likely causes

  • Line or low voltage wiring to the motor
  • No call signal from the thermostat
  • ECM control board fault
  • Failed motor or motor module

Check in this order

  1. Confirm 208-230 VAC on the load side of the control box breaker.
  2. Check the line and low voltage wiring to the motor terminal block.
  3. With a call 24 VAC between G and C on the ECM board (cooling or fan), or W1 and C (heat).
  4. Board check in heat 24 VAC between connector pins 1 and 2. In cooling: pins 1 and 6, and pins 1 and 15. A meter will not read pins 4, 5, 7, 11.
  5. Board puts out the right signals replace the motor or motor control module.

Applies to: NASV/NASS 24B, 36C, 48D, 59D

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 7 Troubleshooting, p.23-24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.