Navien · Air handler troubleshooting
Electric heat model: ECM blower motor not running
What is going on
ECM motor checks with line voltage present.
Likely causes
- Line or low voltage wiring to the motor
- No call signal from the thermostat
- ECM control board fault
- Failed motor or motor module
Check in this order
- Confirm 208-230 VAC on the load side of the control box breaker.
- Check the line and low voltage wiring to the motor terminal block.
- With a call 24 VAC between G and C on the ECM board (cooling or fan), or W1 and C (heat).
- Board check in heat 24 VAC between connector pins 1 and 2. In cooling: pins 1 and 6, and pins 1 and 15. A meter will not read pins 4, 5, 7, 11.
- Board puts out the right signals replace the motor or motor control module.
Applies to: NASV/NASS 24B, 36C, 48D, 59D
More air handler guides
- Air handler or outdoor unit locks out, or transformer burns out (separate transformers)
- Blower does not run, no heat or no cooling: first checks
- Blower runs nonstop and outdoor unit will not start (leak mitigation)
- Electric heat model: constant torque blower motor not running
- Electric heat model: no 24 V control power
- Electric heat short cycles or overshoots the setpoint
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 7 Troubleshooting, p.23-24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.