Navien · Air handler troubleshooting

Air handler or outdoor unit locks out, or transformer burns out (separate transformers)

Navien NAS

What is going on

When the air handler and the outdoor unit each have their own 24 V transformer, tying both to one R terminal (or leaving the RC-RH jumper in) connects two Class 2 circuits together.

Likely causes

  • Both transformers wired to a single R terminal on the thermostat
  • Jumper between RC and RH left in place
  • Thermostat has no separate RC and RH terminals

Check in this order

  1. Power off before rewiring.
  2. Outdoor unit R (red) goes to RC on the thermostat. Air handler red pigtail goes to RH.
  3. Take out the RC-RH jumper if the thermostat has one.
  4. If the thermostat has only one R terminal, it has to be replaced with one that has RC and RH.
  5. Check both transformers; replace one that burnt out.
  6. Run the air handler and the outdoor unit one at a time to confirm each works.

Applies to: NASV/NASS 24B, 36C, 48D, 59D

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAS Series Air Handler Installation and Operation Manual (24-60K, R-454B), 9 Thermostat Wiring and Connections, p.29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.