Navien · Air handler troubleshooting
Air handler or outdoor unit locks out, or transformer burns out (separate transformers)
What is going on
When the air handler and the outdoor unit each have their own 24 V transformer, tying both to one R terminal (or leaving the RC-RH jumper in) connects two Class 2 circuits together.
Likely causes
- Both transformers wired to a single R terminal on the thermostat
- Jumper between RC and RH left in place
- Thermostat has no separate RC and RH terminals
Check in this order
- Power off before rewiring.
- Outdoor unit R (red) goes to RC on the thermostat. Air handler red pigtail goes to RH.
- Take out the RC-RH jumper if the thermostat has one.
- If the thermostat has only one R terminal, it has to be replaced with one that has RC and RH.
- Check both transformers; replace one that burnt out.
- Run the air handler and the outdoor unit one at a time to confirm each works.
Applies to: NASV/NASS 24B, 36C, 48D, 59D
More air handler guides
- Blower does not run, no heat or no cooling: first checks
- Blower runs nonstop and outdoor unit will not start (leak mitigation)
- Electric heat model: constant torque blower motor not running
- Electric heat model: ECM blower motor not running
- Electric heat model: no 24 V control power
- Electric heat short cycles or overshoots the setpoint
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAS Series Air Handler Installation and Operation Manual (24-60K, R-454B), 9 Thermostat Wiring and Connections, p.29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.