Navien · Air handler troubleshooting
Electric heat model: no 24 V control power
What is going on
Electric heat models: line power and 24 V checks at the control box.
Likely causes
- Breaker tripped
- Transformer secondary in-line fuse blown
- Wiring from transformer loose
- Failed transformer
Check in this order
- Check 208-240 VAC on the load side of the control box breakers. None: reset the breaker that tripped and find out why.
- Line voltage present check 24 VAC from the RED pigtail (or R terminal) to ground.
- No 24 VAC check the in-line fuse on the transformer secondary.
- Fuse good check wiring from the transformer to the low voltage terminal block or ECM board.
- Wiring good and 208-240 VAC on the primary: replace the transformer.
Applies to: NASV/NASS 24B, 36C, 48D, 59D
More air handler guides
- Air handler or outdoor unit locks out, or transformer burns out (separate transformers)
- Blower does not run, no heat or no cooling: first checks
- Blower runs nonstop and outdoor unit will not start (leak mitigation)
- Electric heat model: constant torque blower motor not running
- Electric heat model: ECM blower motor not running
- Electric heat short cycles or overshoots the setpoint
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 7 Troubleshooting, p.23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.