Navien · Air handler troubleshooting

Electric heat model: no 24 V control power

Navien NAS

What is going on

Electric heat models: line power and 24 V checks at the control box.

Likely causes

  • Breaker tripped
  • Transformer secondary in-line fuse blown
  • Wiring from transformer loose
  • Failed transformer

Check in this order

  1. Check 208-240 VAC on the load side of the control box breakers. None: reset the breaker that tripped and find out why.
  2. Line voltage present check 24 VAC from the RED pigtail (or R terminal) to ground.
  3. No 24 VAC check the in-line fuse on the transformer secondary.
  4. Fuse good check wiring from the transformer to the low voltage terminal block or ECM board.
  5. Wiring good and 208-240 VAC on the primary: replace the transformer.

Applies to: NASV/NASS 24B, 36C, 48D, 59D

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 7 Troubleshooting, p.23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.