Navien · Air handler troubleshooting
Electric heat model: constant torque blower motor not running
What is going on
Constant torque (5-tap) motor checks.
Likely causes
- Loose BMMP/BMFP plugs
- No line voltage at L and N
- No 24 V on a speed tap
- 3 A secondary fuse blown
- Failed motor
Check in this order
- Check the 6-pin motor plugs BMMP and BMFP.
- With a blower call check 208-240 VAC across motor L and N, and 24 VAC from C to the RED or BLACK speed tap wire.
- Line voltage and 24 V on a tap but no motor: replace the motor.
- No line voltage at the motor check the control board and breaker wiring.
- No 24 V on any tap: check board connections and the 3 A in-line fuse on the transformer secondary.
- Heat call 24 VAC on W at the low voltage terminal block, then on the RED tap wire. Cooling or fan: 24 VAC G to C, then the BLACK tap wire.
- No 24 V at the thermostat G with 24 V at R and a call: replace the thermostat.
Applies to: NASV/NASS 24B, 36C, 48D, 59D
More air handler guides
- Air handler or outdoor unit locks out, or transformer burns out (separate transformers)
- Blower does not run, no heat or no cooling: first checks
- Blower runs nonstop and outdoor unit will not start (leak mitigation)
- Electric heat model: ECM blower motor not running
- Electric heat model: no 24 V control power
- Electric heat short cycles or overshoots the setpoint
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 7 Troubleshooting, p.24-25. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.