Electric heat model: constant torque blower motor not running

Navien NAS

What is going on

Constant torque (5-tap) motor checks.

Likely causes

  • Loose BMMP/BMFP plugs
  • No line voltage at L and N
  • No 24 V on a speed tap
  • 3 A secondary fuse blown
  • Failed motor

Check in this order

  1. Check the 6-pin motor plugs BMMP and BMFP.
  2. With a blower call check 208-240 VAC across motor L and N, and 24 VAC from C to the RED or BLACK speed tap wire.
  3. Line voltage and 24 V on a tap but no motor: replace the motor.
  4. No line voltage at the motor check the control board and breaker wiring.
  5. No 24 V on any tap: check board connections and the 3 A in-line fuse on the transformer secondary.
  6. Heat call 24 VAC on W at the low voltage terminal block, then on the RED tap wire. Cooling or fan: 24 VAC G to C, then the BLACK tap wire.
  7. No 24 V at the thermostat G with 24 V at R and a call: replace the thermostat.

Applies to: NASV/NASS 24B, 36C, 48D, 59D

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 7 Troubleshooting, p.24-25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.