Navien · Air handler troubleshooting

Electric heat short cycles or overshoots the setpoint

Navien NAS

What is going on

On thermostats with an adjustable heat anticipator, the setting for this air handler is 0.4. A wrong setting changes how long each heat cycle runs.

Likely causes

  • Heat anticipator set too low: short cycling
  • Heat anticipator set too high: long cycles, house overshoots then gets cold before the next cycle

Check in this order

  1. Check if the thermostat has an anticipator (self-setting models have none).
  2. Set the anticipator to 0.4.
  3. Run a heat cycle and watch the on time and room temperature swing.

Applies to: NASV/NASS 24B, 36C, 48D, 59D

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAS Series Air Handler Installation and Operation Manual (24-60K, R-454B), 9 Thermostat Wiring and Connections, p.33. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.