Navien · Air handler troubleshooting

Blower runs nonstop and outdoor unit will not start (leak mitigation)

Navien NAS

What is going on

The refrigerant sensor has put the air handler in leak mitigation: blower on, 24 V to the outdoor contactor opened. The ALARM (orange) pigtail drops from 24 VAC to 0 VAC.

Likely causes

  • Real R-454B leak at the indoor coil
  • Refrigerant sensor failed or at end of life (stays in mitigation)

Check in this order

  1. Ventilate the area. No open flames or sparks.
  2. Check for a leak with an A2L-rated portable leak detector.
  3. Leak found repair it. The blower keeps running 5 minutes after the level at the sensor drops below its setpoint.
  4. No leak found but it stays in mitigation replace the sensor with the approved Navien part, same location.
  5. ALARM wire 24 VAC = normal, 0 VAC = leak detected.

Applies to: NASV/NASS 24B, 36C, 48D, 59D

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 8 Refrigerant Leak Detection System, p.28-29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.