Navien · Air handler troubleshooting
Blower runs nonstop and outdoor unit will not start (leak mitigation)
What is going on
The refrigerant sensor has put the air handler in leak mitigation: blower on, 24 V to the outdoor contactor opened. The ALARM (orange) pigtail drops from 24 VAC to 0 VAC.
Likely causes
- Real R-454B leak at the indoor coil
- Refrigerant sensor failed or at end of life (stays in mitigation)
Check in this order
- Ventilate the area. No open flames or sparks.
- Check for a leak with an A2L-rated portable leak detector.
- Leak found repair it. The blower keeps running 5 minutes after the level at the sensor drops below its setpoint.
- No leak found but it stays in mitigation replace the sensor with the approved Navien part, same location.
- ALARM wire 24 VAC = normal, 0 VAC = leak detected.
Applies to: NASV/NASS 24B, 36C, 48D, 59D
More air handler guides
- Air handler or outdoor unit locks out, or transformer burns out (separate transformers)
- Blower does not run, no heat or no cooling: first checks
- Electric heat model: constant torque blower motor not running
- Electric heat model: ECM blower motor not running
- Electric heat model: no 24 V control power
- Electric heat short cycles or overshoots the setpoint
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 8 Refrigerant Leak Detection System, p.28-29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.