TXV coil: checks before replacing the TXV
What is going on
Two quick checks before changing a TXV.
Check in this order
- Refrigerant work only by a certified tech. R-454B is mildly flammable: no open flame or sparks near a leak.
- Slowly loosen the flare nut of the external equalizer at the suction port. A big pressure release is normal: tighten it back. Little or no release means the Schrader core is not being pushed in. Fit an anti-blow-back fitting and test again.
- Take the bulb off and hold it in your hand: high side should drop and low side rise as the valve opens. Put it in ice water: high side should rise and low side drop. No change = bad TXV.
Applies to: NAM24B, NAM36B, NAM36C, NAM48C, NAM59C, NAM59D cased coils with TXV and refrigerant leak sensor
More air handler guides
- Air handler or outdoor unit locks out, or transformer burns out (separate transformers)
- Blower does not run, no heat or no cooling: first checks
- Blower runs nonstop and outdoor unit will not start (leak mitigation)
- Electric heat model: constant torque blower motor not running
- Electric heat model: ECM blower motor not running
- Electric heat model: no 24 V control power
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAM Series cased coil (24-60K, R454B) Installation and Operation Manual, Things to check before replacing TXV p.19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.