TXV coil: checks before replacing the TXV

Navien NAM

What is going on

Two quick checks before changing a TXV.

Check in this order

  1. Refrigerant work only by a certified tech. R-454B is mildly flammable: no open flame or sparks near a leak.
  2. Slowly loosen the flare nut of the external equalizer at the suction port. A big pressure release is normal: tighten it back. Little or no release means the Schrader core is not being pushed in. Fit an anti-blow-back fitting and test again.
  3. Take the bulb off and hold it in your hand: high side should drop and low side rise as the valve opens. Put it in ice water: high side should rise and low side drop. No change = bad TXV.

Applies to: NAM24B, NAM36B, NAM36C, NAM48C, NAM59C, NAM59D cased coils with TXV and refrigerant leak sensor

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAM Series cased coil (24-60K, R454B) Installation and Operation Manual, Things to check before replacing TXV p.19. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.