TXV coil: checking a TXV you think is bad

Navien NAM

What is going on

Order of checks before blaming the TXV on a NAM coil.

Likely causes

  • Wrong charge
  • Dirty coils or filter, low airflow
  • Plugged TXV inlet strainer or liquid line drier
  • Bad TXV

Check in this order

  1. Refrigerant work only by a certified tech. R-454B is mildly flammable: no open flame or sparks near a leak.
  2. Put gauges on. Compare pressures, subcooling and superheat to the outdoor unit charging chart. Typical: about 10 F subcooling at the outdoor liquid valve and 8-12 F superheat at the outdoor valve, but go by that unit's chart.
  3. Check indoor airflow. Clean dirty coils and change the filter first.
  4. Get the charge right, weighing it in if needed, then read pressures again.
  5. Pull the sensing bulb off the suction line. No change in readings = TXV is bad.
  6. Put the bulb in ice water. Still no change = TXV is likely bad.
  7. Still off with a good TXV look at the TXV inlet strainer and the liquid line drier.

Applies to: NAM24B, NAM36B, NAM36C, NAM48C, NAM59C, NAM59D cased coils with TXV and refrigerant leak sensor

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAM Series cased coil (24-60K, R454B) Installation and Operation Manual, 3.7 TXV Troubleshooting p.18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.