Two-piece unit external static (cased coil with gas furnace or modular blower)
What is going on
Used when an EEV cased coil is paired with a gas furnace or modular blower. Clean filters must be installed. Readings are taken at the furnace or modular blower.
Likely causes
- Closed dampers or registers
- Undersized or oversized ductwork
- Dirty filter or electronic air cleaner restriction
Check in this order
- With clean filters installed, measure return static at the inlet of the gas furnace or modular blower. This is negative.
- If a filter is installed with the furnace, measure between the filter and the furnace.
- Measure supply static at the outlet of the furnace or modular blower. This is positive.
- Add the two readings for total external static. Include any electronic air cleaner in the reading.
- Use the furnace or modular blower airflow chart to find CFM.
- If total static is outside the allowed range, check dampers, registers and duct layout.
Applies to: EEV cased coil with gas furnace or modular blower
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.