Daikin · Air handler troubleshooting
Check transformer and control circuit voltage
What is going on
The indoor unit has a step-down transformer (208/230 or 115 V primary to 24 V secondary) that feeds the control circuit. The outdoor section has no transformer. Use this check when the control circuit has no 24 V.
Likely causes
- Faulty transformer
- Bad wiring or splices on the control circuit
- No line voltage at the transformer primary
Check in this order
- Disconnect power, then remove the control panel cover to reach the transformer.
- Restore power and measure voltage across the transformer secondary (R to C) with a voltmeter.
- If there is no voltage, the transformer, wiring or splices are at fault. Check the primary voltage at the incoming line connections or splices.
- If line voltage is present at the primary and the wiring and splices are good, replace the transformer.
Applies to: Indoor air handler / cased coil with control transformer
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.