Daikin · Air handler troubleshooting

Check transformer and control circuit voltage

DV**FECDFVE**CAPE(A)*CHPE*

What is going on

The indoor unit has a step-down transformer (208/230 or 115 V primary to 24 V secondary) that feeds the control circuit. The outdoor section has no transformer. Use this check when the control circuit has no 24 V.

Likely causes

  • Faulty transformer
  • Bad wiring or splices on the control circuit
  • No line voltage at the transformer primary

Check in this order

  1. Disconnect power, then remove the control panel cover to reach the transformer.
  2. Restore power and measure voltage across the transformer secondary (R to C) with a voltmeter.
  3. If there is no voltage, the transformer, wiring or splices are at fault. Check the primary voltage at the incoming line connections or splices.
  4. If line voltage is present at the primary and the wiring and splices are good, replace the transformer.

Applies to: Indoor air handler / cased coil with control transformer

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.