Daikin · Air handler troubleshooting
Duct static pressure and coil pressure drop
What is going on
Static pressure limits for the indoor section are in the specifications. Too much external static can starve the coil and cause icing. Too little airflow can cause poor humidity control and condensate carryover. Too much airflow can overload the motor.
Likely causes
- Closed dampers or registers
- Undersized or poorly laid out ductwork
- Dirty or restricted filters
Check in this order
- Check the minimum and maximum allowable duct static in the specifications.
- Use the coil airflow vs. pressure drop table for the coil.
- If the external static is outside the allowed range, check for closed dampers, registers, and poor duct layout.
Applies to: Indoor air handler and cased coil airflow
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.