Daikin · Air handler troubleshooting
Blower not running: EEM motor air handler
What is going on
Quick check for an EEM (constant torque) blower motor that will not run.
Check in this order
- Kill power at the disconnect before working in the unit. There can be more than one power source.
- Check for 240 V on motor terminals L and N. No voltage: check breaker, fuses and wiring.
- Check for 24 V between C and the tap terminal in use. No voltage: make sure the thermostat is calling for fan and check the low voltage fuse and wiring.
- With both voltages present and the motor not running, replace the motor or module.
Applies to: Air handlers used with DC3S/DC4S/DC5S and DH4S/DH5S units
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Troubleshooting chart Air Handler - EEM Motor p.46; Checking High Efficiency Motors p.26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.