Blower not running: EEM motor air handler

Daikin R-32 DC3S/DC4S/DC5SDaikin R-32 DH4S/DH5S

What is going on

Quick check for an EEM (constant torque) blower motor that will not run.

Check in this order

  1. Kill power at the disconnect before working in the unit. There can be more than one power source.
  2. Check for 240 V on motor terminals L and N. No voltage: check breaker, fuses and wiring.
  3. Check for 24 V between C and the tap terminal in use. No voltage: make sure the thermostat is calling for fan and check the low voltage fuse and wiring.
  4. With both voltages present and the motor not running, replace the motor or module.

Applies to: Air handlers used with DC3S/DC4S/DC5S and DH4S/DH5S units

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Troubleshooting chart Air Handler - EEM Motor p.46; Checking High Efficiency Motors p.26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.