Daikin · Air handler troubleshooting
No auxiliary electric heat
What is going on
Check order when the electric heat strips do not come on.
Check in this order
- Kill power at the disconnect before working in the unit. There can be more than one power source.
- Check power at the disconnect and 240 V at the breakers or heater contactors. Replace bad breakers or wiring.
- Check 24 V at the transformer. No 24 V: replace the transformer.
- Check 24 V on W at the contactor. Missing: check the thermostat and wiring.
- 24 V on the coil but the contactor stays open: replace the contactor.
- Check the limit switch. Replace it if open.
- Check the fusible links. Replace open links.
- Ohm the heat strips. No continuity: replace the strip.
Applies to: Air handlers used with DC3S/DC4S/DC5S and DH4S/DH5S units
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Troubleshooting chart Auxiliary Electric - Heating p.47; Checking Heater Elements / Limit / Fuse Link p.32-33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.