Daikin · Air handler troubleshooting

Check external static pressure on a two-piece indoor unit

DV**FEC / DFVE**CAPE(A)* / CHPE*

What is going on

Used for an EEV cased coil paired with a gas furnace or modular blower. Total external static is the sum of the return and supply readings. Use it to find the airflow (CFM) from the furnace or blower chart.

Likely causes

  • Closed dampers or registers
  • Undersized or oversized or poorly laid out ductwork
  • Dirty or restrictive filter, or an electronic air cleaner adding restriction

Check in this order

  1. Start with clean filters in the indoor unit.
  2. Measure return static at the inlet of the gas furnace or modular blower with an inclined manometer or Magnehelic gauge. The reading is negative (example -0.30 inH2O / -74.7 Pa).
  3. If a filter is installed with the furnace, measure between the filter and the furnace instead.
  4. Measure supply static at the outlet of the gas furnace or modular blower. The reading is positive (example 0.20 inH2O / 49.8 Pa).
  5. Add the absolute values of the two readings to get total external static (example 0.50 inH2O / 124.5 Pa). Both can be read at once on the manometer.
  6. Include any electronic air cleaner in the reading if one is installed.
  7. Look up the airflow (CFM) for that static on the furnace or modular blower chart.
  8. If total static is above the allowed maximum or below the minimum, check for closed dampers, registers and duct layout.

Applies to: Two-piece EEV cased coil with gas furnace or modular blower

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SiUS612209EA service instructions, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.