Cooling emergency mode - EEV air handler

DFVE EEV air handler with outdoor unit

What is going on

The indoor unit provides airflow on its own and the outdoor unit runs at a set cooling level. Both units run independently in this mode.

Check in this order

  1. Select the airflow on the indoor unit with DS-4 S-13 and S-14 (25 percent, 50 percent, 75 percent or 100 percent).
  2. On indoor DS-6, set S-21 to ON and S-22 to OFF to enable emergency indoor fan operation.
  3. Select the cooling level on the outdoor unit DS-2 (Low, Medium or High). See the DS-2 table.
  4. When communication is restored, return all these switches to default settings.

Applies to: DFVE EEV air handler with DX6VS/DZ6VS outdoor unit

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 34. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.