Navien · Air handler troubleshooting

Testing the refrigerant leak mitigation system (commissioning check)

Navien NAS

What is going on

How to prove the R-454B leak sensor actually shuts down the outdoor unit and runs the blower. Do it at start-up or when you suspect the sensor or its wiring.

Likely causes

  • Sensor wiring loose, damaged or unplugged (sensor goes into mitigation and stays there)
  • Outdoor contactor wire not run through the sensor Y-CC pigtail and COM on the low voltage strip, so the compressor is not cut off
  • Failed sensor

Check in this order

  1. Use an A2L-rated leak detector. No open flame or sparks near the unit.
  2. Pull the coil access panel. The black sensor sits low at the front of the coil.
  3. Cooling test thermostat on COOL, fan AUTO, setpoint below room temp. Wait for the compressor to start.
  4. Within 30 seconds of compressor start, give the sensor a small puff of refrigerant.
  5. Compressor and outdoor fan must drop out, indoor blower keeps running, and the orange ALARM pigtail reads 0 VAC (24 VAC = normal).
  6. About 5 minutes after the refrigerant clears the sensor, the outdoor unit should come back on with the blower still running.
  7. Off-cycle test thermostat OFF, wait for everything to stop, puff the sensor again.
  8. Blower must start and ALARM must read 0 VAC. Blower should stop about 5 minutes after the refrigerant clears.
  9. If it does not act like this check the wiring against the unit diagram (Y-CC pigtail and COM for the outdoor control wire). Wiring good = replace the sensor with the Navien part.
  10. Refit the panel and set the thermostat back.

Applies to: NASV/NASS 24B, 36C, 48D, 59D

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAS Series Air Handler Installation and Operation Manual (24-60K, R-454B), 7 Refrigerant Leak Detection System, p.23 and p.25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.