S-4 Checking transformer and control circuit

DV**FECDFVE**CAPE(A)*CHPE*

What is going on

Each indoor unit has a step-down transformer (208/230 or 115 V primary to 24 V secondary). The outdoor sections have no transformer.

Likely causes

  • No secondary voltage can mean a faulty transformer, bad wiring or bad splices
  • Transformer inoperative if primary voltage is present but secondary is not

Check in this order

  1. Disconnect all power before servicing.
  2. Remove the control panel cover to access the transformer.
  3. With power on, check voltage across the transformer secondary (R to C) with a voltmeter.
  4. If there is no voltage, check transformer primary voltage at the incoming line connections or splices.
  5. If line voltage is present at the primary and wiring and splices are good, replace the transformer.

Applies to: Daikin EEV air handlers and cased coils

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EB service instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.