S-4 Checking transformer and control circuit
What is going on
Each indoor unit has a step-down transformer (208/230 or 115 V primary to 24 V secondary). The outdoor sections have no transformer.
Likely causes
- No secondary voltage can mean a faulty transformer, bad wiring or bad splices
- Transformer inoperative if primary voltage is present but secondary is not
Check in this order
- Disconnect all power before servicing.
- Remove the control panel cover to access the transformer.
- With power on, check voltage across the transformer secondary (R to C) with a voltmeter.
- If there is no voltage, check transformer primary voltage at the incoming line connections or splices.
- If line voltage is present at the primary and wiring and splices are good, replace the transformer.
Applies to: Daikin EEV air handlers and cased coils
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EB service instructions, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.