Daikin · Air handler troubleshooting
Running the UltraCheck-EZ ECM diagnostic tool
What is going on
The tool sends a run signal to the ECM motor and shows communication status. Use the indication table to decide whether to replace the control or the motor.
Likely causes
- Tool fuse open or tool not on 24 VAC
- Motor control/end bell fault
- Motor winding fault
Check in this order
- Disconnect power to the indoor unit.
- Disconnect the 4-circuit control harness from the motor.
- Plug the 4-circuit connector from the tool into the motor control connector.
- Clip one alligator clip to a ground source and the other to a 24 VAC source. The clips are not polarized.
- Do not connect the tool to any source other than 24 VAC, as this blows its non-replaceable fuse.
- Turn on power to the indoor unit.
- Press the orange power button to start the motor, and allow up to 5 seconds to start.
- Read the green LED and motor action against the indication table.
- Press the orange power button to stop the motor, disconnect power and the tool.
- Reconnect the 4-wire harness from the control board to the motor.
Applies to: Emerson UltraCheck ECM motors
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.