Daikin · Air handler troubleshooting

Running the UltraCheck-EZ ECM diagnostic tool

DFVEDV**FEC

What is going on

The tool sends a run signal to the ECM motor and shows communication status. Use the indication table to decide whether to replace the control or the motor.

Likely causes

  • Tool fuse open or tool not on 24 VAC
  • Motor control/end bell fault
  • Motor winding fault

Check in this order

  1. Disconnect power to the indoor unit.
  2. Disconnect the 4-circuit control harness from the motor.
  3. Plug the 4-circuit connector from the tool into the motor control connector.
  4. Clip one alligator clip to a ground source and the other to a 24 VAC source. The clips are not polarized.
  5. Do not connect the tool to any source other than 24 VAC, as this blows its non-replaceable fuse.
  6. Turn on power to the indoor unit.
  7. Press the orange power button to start the motor, and allow up to 5 seconds to start.
  8. Read the green LED and motor action against the indication table.
  9. Press the orange power button to stop the motor, disconnect power and the tool.
  10. Reconnect the 4-wire harness from the control board to the motor.

Applies to: Emerson UltraCheck ECM motors

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.