Daikin · Air handler troubleshooting

Reading the state, error and airflow on the 2-digit display

DV**FECDFVE**CAPE(A)*CHPE*

What is going on

With the indoor unit powered, the 2-digit display cycles through the current state, any error code and the estimated airflow. The EEV cased coil does not show airflow. During a minor error in defrost or emergency mode the display shows the state with the error.

Check in this order

  1. Read the state shown first (for example FC, FH, dF, or EE).
  2. If an error code is present in standby or normal mode, the display keeps showing it. Look it up in the indoor error code table.
  3. To read airflow, watch for the "A" indicator, then the upper two digits and the lower two digits of CFM shown in turn. Example: 1240 CFM shows "A", "12", then "40".
  4. During a minor error in defrost, the display shows dF, then the error code, then airflow.
  5. During a minor error in emergency mode, the display shows EE, then the error code.

Applies to: EEV indoor units with 2-digit 7-segment display. The EEV cased coil does not indicate airflow.

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 26-27. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.