Daikin · Air handler troubleshooting

No 24 VAC control voltage from indoor transformer

DFVEDV**FEC

What is going on

The indoor unit has a step-down transformer (208/230 or 115 V primary to 24 V secondary). The outdoor section has no transformer. Use this check when the control circuit has no 24 V.

Likely causes

  • Faulty transformer
  • Bad wiring or splices
  • No line voltage at the transformer primary

Check in this order

  1. Disconnect power, remove the control panel cover to reach the transformer, then restore power for measurement.
  2. With power on, measure voltage across the transformer secondary (R to C).
  3. If there is no voltage, check the wiring and splices.
  4. Check primary voltage at the incoming line connections or splices.
  5. If line voltage is present at the primary and the wiring is good, replace the transformer.

Applies to: Indoor unit transformer, 24 V control circuit

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.