Daikin · Air handler troubleshooting
No 24 VAC control voltage from indoor transformer
What is going on
The indoor unit has a step-down transformer (208/230 or 115 V primary to 24 V secondary). The outdoor section has no transformer. Use this check when the control circuit has no 24 V.
Likely causes
- Faulty transformer
- Bad wiring or splices
- No line voltage at the transformer primary
Check in this order
- Disconnect power, remove the control panel cover to reach the transformer, then restore power for measurement.
- With power on, measure voltage across the transformer secondary (R to C).
- If there is no voltage, check the wiring and splices.
- Check primary voltage at the incoming line connections or splices.
- If line voltage is present at the primary and the wiring is good, replace the transformer.
Applies to: Indoor unit transformer, 24 V control circuit
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.