Daikin · Air handler troubleshooting

Navigating the EEV indoor unit mode display for error history

DV**FECDFVE**CAPE(A)*CHPE*

What is going on

The 2-digit display is a backup to the thermostat for reading the six most recent EEV indoor faults and for erasing the history. Navigation depends on how long the FAULT RECALL button is held and released. The flowchart on the source page is partly unclear, so verify each press with the display.

Check in this order

  1. Start from screen zero (no display, standby).
  2. Hold FAULT RECALL for more than 2 seconds, then release between 2 and 5 seconds. The first (most recent) error code appears flashing.
  3. Press FAULT RECALL to step to the next error code. Repeat to reach the last code.
  4. Hold FAULT RECALL for more than 5 seconds to reach the erase step. The display shows a solid "88" for 3 seconds before all diagnostic codes are erased.
  5. If the display is idle for 3 minutes, the unit returns to screen zero.

Applies to: EEV indoor units

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 28-29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.