Daikin · Air handler troubleshooting

Measuring total external static pressure on a two-piece indoor unit

DV**FECDFVE**CAPE(A)*CHPE*

What is going on

For an EEV cased coil paired with a gas furnace or modular blower, add the return and supply static readings to get total external static. Use the airflow chart of the furnace or blower to find CFM at that static.

Check in this order

  1. Install clean filters in the indoor unit.
  2. With a draft gauge (inclined manometer or Magnehelic), measure return static at the inlet of the furnace or modular blower. This reading is negative (example: -0.30 inH2O / -74.7 Pa).
  3. If a filter is installed with the furnace, measure return static between the filter and the furnace.
  4. Measure supply static at the outlet of the furnace or modular blower. This reading is positive (example: 0.20 inH2O / 49.8 Pa).
  5. Add the absolute values of the two readings for total external static (example: 0.30 + 0.20 = 0.50 inH2O, or 124.5 Pa).
  6. Include any electronic air cleaner in the readings if one is used.
  7. Read CFM from the furnace or blower airflow chart at the measured static.
  8. If static is above the maximum or below the minimum allowed, check for closed dampers or registers and for undersized, oversized or poorly laid out ductwork.

Applies to: Two-piece EEV cased coil with gas furnace or modular blower

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.