Measuring air handler external static

DFVEDV**FEC

What is going on

Total external static is the absolute sum of the return (negative) and supply (positive) static readings. Example: -0.30 inH2O + 0.20 inH2O = 0.50 inH2O (-74.7 Pa + 49.8 Pa = 124.5 Pa).

Likely causes

  • Restriction in return or supply duct
  • Dirty filter

Check in this order

  1. Using a draft gauge (inclined manometer), measure return static at the unit inlet. This is negative.
  2. If a filter is installed, measure between the filter and the air handler.
  3. Measure supply static in the supply duct. This is positive.
  4. Add the two readings to get total external static. Both can be read at once on the manometer.
  5. Use the airflow table to find CFM at the measured static.

Applies to: Air handler external static pressure

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.