Measuring air handler external static
What is going on
Total external static is the absolute sum of the return (negative) and supply (positive) static readings. Example: -0.30 inH2O + 0.20 inH2O = 0.50 inH2O (-74.7 Pa + 49.8 Pa = 124.5 Pa).
Likely causes
- Restriction in return or supply duct
- Dirty filter
Check in this order
- Using a draft gauge (inclined manometer), measure return static at the unit inlet. This is negative.
- If a filter is installed, measure between the filter and the air handler.
- Measure supply static in the supply duct. This is positive.
- Add the two readings to get total external static. Both can be read at once on the manometer.
- Use the airflow table to find CFM at the measured static.
Applies to: Air handler external static pressure
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.