Daikin · Air handler troubleshooting
Measure two-piece unit external static (S-203A)
What is going on
A two-piece unit is an EEV cased coil with a gas furnace or modular blower. External static is measured at the furnace or modular blower.
Likely causes
- Restricted return or supply duct
- Closed dampers or registers
- Dirty filter or electronic air cleaner loading
Check in this order
- With clean filters in the indoor unit, measure return static at the inlet of the gas furnace or modular blower (negative pressure).
- If a filter is in the return, measure between the filter and the furnace or blower.
- Measure supply static at the outlet of the gas furnace or modular blower (positive pressure).
- Add the two absolute readings for total external static. Include any electronic air cleaner in the readings.
- Use the airflow chart for the gas furnace or modular blower to find CFM at the measured static.
- If total static is outside the minimum or maximum, check for closed dampers, registers, and undersized or oversized poorly laid out ductwork.
Applies to: EEV cased coil with gas furnace or modular blower
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.