Daikin · Air handler troubleshooting
Measure air handler external static (S-203)
What is going on
External static is the sum of the absolute values of the return and supply static readings.
Likely causes
- Restricted return or supply duct
- Dirty filter
Check in this order
- With a draft gauge (inclined manometer), measure return duct static at the unit inlet (negative pressure). If a filter is installed, measure between the filter and the air handler.
- Measure supply duct static (positive pressure).
- Add the two absolute readings for total external static. Example: -0.30 inH2O + 0.20 inH2O = 0.50 inH2O (-74.7 Pa + 49.8 Pa = 124.5 Pa).
- Use the airflow table for the air handler to find CFM at that total external static.
Applies to: DV**FEC / DFVE** air handlers
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.