Daikin · Air handler troubleshooting

Measure air handler external static (S-203)

DV**FECDFVE**

What is going on

External static is the sum of the absolute values of the return and supply static readings.

Likely causes

  • Restricted return or supply duct
  • Dirty filter

Check in this order

  1. With a draft gauge (inclined manometer), measure return duct static at the unit inlet (negative pressure). If a filter is installed, measure between the filter and the air handler.
  2. Measure supply duct static (positive pressure).
  3. Add the two absolute readings for total external static. Example: -0.30 inH2O + 0.20 inH2O = 0.50 inH2O (-74.7 Pa + 49.8 Pa = 124.5 Pa).
  4. Use the airflow table for the air handler to find CFM at that total external static.

Applies to: DV**FEC / DFVE** air handlers

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.