Navien · Air handler troubleshooting

Leak sensor: wiring check

Navien NAM

What is going on

How the NAM leak sensor harness is wired, for checking a no-cool or blower problem after install.

Likely causes

  • Pigtail on the wrong terminal
  • Y-CC wire landed on the contactor common

Check in this order

  1. Kill power at the disconnect before working in the unit. There can be more than one power source.
  2. RED (R) goes to R on the furnace terminal block.
  3. BLACK (COM) goes to C.
  4. YELLOW (Y-Tstat) goes to Y or Y1 on the furnace (or the thermostat Y wire).
  5. WHITE (Y-CC) goes to the Y wire going to the outdoor unit contactor. Never to the contactor common.
  6. BLUE (G) goes to G on the furnace.
  7. ORANGE (ALARM) is capped from the factory. It has 24 VAC with no leak and drops to 0 VAC during a leak. Use it only for a BMS or smart thermostat alert.
  8. Make sure continuous fan speed gives at least the minimum mitigation airflow in Table 4 for the system charge.

Applies to: NAM24B, NAM36B, NAM36C, NAM48C, NAM59C, NAM59D cased coils with TXV and refrigerant leak sensor

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAM Series cased coil (24-60K, R454B) Installation and Operation Manual, Refrigerant detection system wiring connections and minimum airflow p.20-22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.