Navien · Air handler troubleshooting
Leak sensor: wiring check
What is going on
How the NAM leak sensor harness is wired, for checking a no-cool or blower problem after install.
Likely causes
- Pigtail on the wrong terminal
- Y-CC wire landed on the contactor common
Check in this order
- Kill power at the disconnect before working in the unit. There can be more than one power source.
- RED (R) goes to R on the furnace terminal block.
- BLACK (COM) goes to C.
- YELLOW (Y-Tstat) goes to Y or Y1 on the furnace (or the thermostat Y wire).
- WHITE (Y-CC) goes to the Y wire going to the outdoor unit contactor. Never to the contactor common.
- BLUE (G) goes to G on the furnace.
- ORANGE (ALARM) is capped from the factory. It has 24 VAC with no leak and drops to 0 VAC during a leak. Use it only for a BMS or smart thermostat alert.
- Make sure continuous fan speed gives at least the minimum mitigation airflow in Table 4 for the system charge.
Applies to: NAM24B, NAM36B, NAM36C, NAM48C, NAM59C, NAM59D cased coils with TXV and refrigerant leak sensor
More air handler guides
- Air handler or outdoor unit locks out, or transformer burns out (separate transformers)
- Blower does not run, no heat or no cooling: first checks
- Blower runs nonstop and outdoor unit will not start (leak mitigation)
- Electric heat model: constant torque blower motor not running
- Electric heat model: ECM blower motor not running
- Electric heat model: no 24 V control power
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAM Series cased coil (24-60K, R454B) Installation and Operation Manual, Refrigerant detection system wiring connections and minimum airflow p.20-22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.