Navien · Air handler troubleshooting
Leak sensor: verification test
What is going on
How to test the leak mitigation system on a NAM coil.
Check in this order
- Refrigerant work only by a certified tech. R-454B is mildly flammable: no open flame or sparks near a leak.
- Take off the coil access panel. The black sensor is near the bottom front of the coil.
- Cooling test thermostat to COOL, fan AUTO, set below room temp. Confirm the compressor runs.
- Within 30 seconds of compressor start, let a small amount of refrigerant out at the sensor.
- Outdoor compressor and fan should stop, the indoor blower should keep running, and the ALARM wire should have no 24 V.
- About 5 minutes after the gas stops, the outdoor unit should come back on.
- Off-cycle test thermostat OFF, wait for everything to stop, release a little gas at the sensor. The blower should start and ALARM should lose 24 V. The blower should stop about 5 minutes after the gas stops.
- If it does not work this way, check for loose or wrong wiring. Wiring good: replace the sensor.
- Put the panel back and set the thermostat back.
Applies to: NAM24B, NAM36B, NAM36C, NAM48C, NAM59C, NAM59D cased coils with TXV and refrigerant leak sensor
More air handler guides
- Air handler or outdoor unit locks out, or transformer burns out (separate transformers)
- Blower does not run, no heat or no cooling: first checks
- Blower runs nonstop and outdoor unit will not start (leak mitigation)
- Electric heat model: constant torque blower motor not running
- Electric heat model: ECM blower motor not running
- Electric heat model: no 24 V control power
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAM Series cased coil (24-60K, R454B) Installation and Operation Manual, Verifying proper functioning of refrigerant leak mitigation system p.22-23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.