Navien · Air handler troubleshooting

Leak sensor: verification test

Navien NAM

What is going on

How to test the leak mitigation system on a NAM coil.

Check in this order

  1. Refrigerant work only by a certified tech. R-454B is mildly flammable: no open flame or sparks near a leak.
  2. Take off the coil access panel. The black sensor is near the bottom front of the coil.
  3. Cooling test thermostat to COOL, fan AUTO, set below room temp. Confirm the compressor runs.
  4. Within 30 seconds of compressor start, let a small amount of refrigerant out at the sensor.
  5. Outdoor compressor and fan should stop, the indoor blower should keep running, and the ALARM wire should have no 24 V.
  6. About 5 minutes after the gas stops, the outdoor unit should come back on.
  7. Off-cycle test thermostat OFF, wait for everything to stop, release a little gas at the sensor. The blower should start and ALARM should lose 24 V. The blower should stop about 5 minutes after the gas stops.
  8. If it does not work this way, check for loose or wrong wiring. Wiring good: replace the sensor.
  9. Put the panel back and set the thermostat back.

Applies to: NAM24B, NAM36B, NAM36C, NAM48C, NAM59C, NAM59D cased coils with TXV and refrigerant leak sensor

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NAM Series cased coil (24-60K, R454B) Installation and Operation Manual, Verifying proper functioning of refrigerant leak mitigation system p.22-23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.